For a small homelab, start with the 12V, 5A Phidgets PSU4018_0 and a compatible DC distribution unit if the loads fit the limits of both. For a full-width rack that needs more outlets, choose the Altronix R1224DC16CB if the loads fit its 2A per-outlet limit and its shared group limits. Keep separate adapters for gear whose power requirements the shared supply cannot meet. Phidgets specifications, Altronix specifications, StarTech compatibility guide.
Power supplies for small and full-width racks
| Best fit | Supply | What decides the fit |
|---|---|---|
| Small rack or shelf with a separate DC power distribution unit (PDU) | Phidgets PSU4018_0 | 12V DC, 5A, 60W, with a center-positive 5.5 × 2.1 mm DC connection. Budget for a compatible PDU and the regional AC plug, which Phidgets sells separately. Phidgets specifications |
| Standard 19-inch rack with many low-current loads | Altronix R1224DC16CB | At 12V, 18A total across 16 outputs with resettable protection. Each group of four shares 4.5A, and each output is limited to 2A. It uses removable terminal blocks and requires 115V AC at 60 Hz. Altronix specifications |
The Altronix also supports 24V DC. Confirm 12V output before connecting 12V equipment. Altronix specifications.
If you already own a DeskPi DP-0042, add the loads on the front and rear jacks of each channel. They share a 3A limit, and the unit accepts up to 8A total. Its output follows its input voltage. Check the PDU input connector and polarity against the brick before ordering. DeskPi documentation, StarTech compatibility guide.
Check which adapters you can remove
- Voltage. Read the power specification for your exact device model. Include devices specified for 12V DC. StarTech compatibility guide.
- Polarity and plug. For each device with a barrel jack, record its polarity and both barrel dimensions. The Phidgets 5.5 × 2.1 mm connection and the 5.5 × 2.5 mm N-type barrel plug described in a reply on the StarTech page differ in the smaller dimension. Before buying, match the plug’s listed outer diameter to the jack’s hole diameter and the plug’s listed inner diameter to the jack’s center-pin diameter. Match polarity as well. Check all three at the brick-to-PDU input and at both ends of each device lead. Phidgets specifications, StarTech compatibility guide.
- Current. Record each device’s specified current and assign it to an output that can supply that much. StarTech compatibility guide.
If any connection in a device’s power path lacks a confirmed match, keep its original adapter. StarTech compatibility guide.
Work out the current budget
Add the specified currents for all 12V devices you plan to power together. Compare the result with the supply and the PDU’s input limit. Then check each output and any shared group. DeskPi documentation, Altronix specifications.
| Example 12V loads | Current |
|---|---|
| Device A | 2 A |
| Device B | 1.5 A |
| Device C | 0.25 A |
| Combined | 3.75 A |
In this example, 3.75A at 12V is 45W. A 5A supply leaves 1.25A of rated capacity. If the brick and DeskPi input pass the compatibility checks above, put the 2A and 1.5A loads on separate channels. Together they would exceed the 3A cap on a single channel. Phidgets specifications, DeskPi documentation.
On the Altronix, a hypothetical group with 2A, 2A and 1A loads adds up to 5A. Each load fits a single outlet, but the group exceeds 4.5A. Assign the 1A load to a different group with room for it. Altronix specifications.
Evidence and limits. In this documentary guide, specifications were checked against the manufacturer pages for the Phidgets PSU4018_0, DeskPi DP-0042 and Altronix R1224DC16CB on November 26, 2026. The load examples are illustrative. No hands-on testing was performed.